The ZW32-12G Outdoor Vacuum Circuit Breaker
PRODUCT PARAMETERS
Item |
Unit |
Parameter |
||
Voltage, current parameters |
|
|
||
Rated voltage |
kV |
12 |
||
Rated short time power frequency withstand voltage (1min) |
kV |
42/48 |
||
Rated lightning impulse withstand voltage (peak) |
kV |
75/85 |
||
Rated frequency |
Hz |
50/60 |
||
Rated current |
A |
630 |
1250 |
|
Rated short-circuit breaking current |
kA |
20 |
||
Rated short-time withstand current (RMS) |
kA |
20 |
||
Rated peak withstand current |
kA |
50 |
||
Rated short-circuit closing current |
kA |
50 |
||
Rated single / back-to-back capacitor bank breaking current |
A |
630/400 |
||
Rated short-circuit current duration |
S |
4 |
||
Rated short-circuit current breaking times |
Times |
50 |
||
The main circuit resistance |
μΩ |
≤80(140) |
||
Rated operational voltage |
|
AC/DC≌220 |
||
Mechanical life |
Times |
10000 |
||
The overcurrent regulating ☆ |
A |
1~10 |
||
Quick-break current |
A |
6~20 |
||
The delay time |
ms |
40~850 |
||
Remote control distance |
m |
> 30 |
||
Reclose time |
Times |
0~3 |
||
Rated operating sequence |
|
O-0.3s-CO-180s-CO |
||
CT |
Ratio |
A |
()/5 |
|
Capacity |
VA |
15 |
||
The output voltage |
A |
AC220 |
||
The output capacity |
W |
600 |
||
The overcurrent regulating |
A |
1~10 |
||
The delay time |
ms |
40~850 |
||
Remote control distance |
m |
30 |
||
Product Features
Fully Sealed Structure:
Provides excellent sealing for moisture and condensation resistance, ideal for harsh and humid climates.
Epoxy Resin Insulation:
Uses imported outdoor epoxy resin or silicone rubber-coated solid insulation, offering high durability against UV, aging, and temperature extremes.
Spring Operating Mechanism:
Features a compact, low-energy mechanism with a small motor power requirement and minimal moving parts, ensuring high reliability and durability.
Multi-Mode Operation:
Supports manual, electric, and remote-control operations.
Can be paired with smart controllers for distribution automation or reclosing devices for fault isolation and sectionalizing.
Integrated Current Transformer:
Configurable with two or three-phase transformers for overcurrent or short-circuit protection and data acquisition.
Optional Isolation Switch:
Includes a three-phase linkage isolation switch with visible disconnect points and anti-misoperation interlocks.
Operating Conditions
Ambient temperature: Maximum +40°C, minimum -40°C
Altitude: ≤2000m
Wind pressure: ≤700Pa (equivalent to a wind speed of 34m/s)
Pollution grade: Level IV
Seismic intensity: ≤8 degrees
Environment: Free of flammable/explosive materials, chemical corrosion, or significant vibration.
Contact Information
For more details, please contact us:
Company Name: KENJING GROUP Co., Ltd.
Phone: +86-15888718229
Email: john@china-kenjing.com